Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/02/2007 | PLUMBING - FINAL | Approved | GAS TAG PREVIOUSLY RELEASED. ALL CONNECTIONS AT PAINT BOOTH APPEAR CODE COMPLIANT | |
| 04/30/2003 | PLUMBING - FINAL | Denied | NEED REVISED PLAN FOR MED PRESSURE GAS TO PAINT BOOTH. | |
| 04/24/2003 | PLUMBING - FINAL | Denied | IVRS - Inspection 0999*WHERE UNIONS ARE NECESSARY, A RIGHT LEFT NIPPLE AND COUPLING SHALL BE USED. 2.) I WILL NOT RELEASE GAS UNTIL T.I. ON PAINT BOOTHS IS APPROVED. |
|
| 04/10/2003 | PLUMBING - FINAL | Partial Approval | IVRS - Inspection 0000*1.) PE UNDERGROUND W/SINGLE PIECE TRANSITION RISERS OK 60# TEST FOR MEDIUM PRESSURE OK 2.) CONTRACTOR TO INSURE PLACEMENT OF #18 AND THEN MAY COVER. |