Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/10/2003 | PLUMBING - FINAL | Approved | IVRS - Inspection 0000* 1.) GAS PRESSURE TEST IS OK 2.) GAS SHUT OFF VALVES OK 3.) WATER HTR FLU VENT, P & T VALVE & DRAIN IS OK 4.) FURANCE FLU VENT IS OK 5.) OK TO BACKFILL TRENCH. |
|
| 04/08/2003 | PLUMBING - FINAL | Denied | IVRS - Inspection 0999* 1.) MUST EXTEND RISER BY METER. 2.) MUST APPLY TAPE YELLOW PRIMER ON ALL FITTINGS AND WRENCH MARKS THEN APPLY 10-MIL TAPE. 3.) MUST EXTEND FLU VENT FOR WATER HTR 3' ABOVE COOLER. 4.) MUST REMOVE FLEX LINE IN P & T DRAIN AND INCREASE TO 3/4". 5.) MUST PROVIDE ROOF JACKS FOR ALL ROOF PENETRATIONS. 6.) MUST BLOCK GAS LINE AND STRAP DOWN EVERY 6'. 7.) RE TEST SYSTEM 10LBS MIN. |