Permit: T03PL00639

Parcel: 13626034B


Addresses:

3422 S FAIRBANKS AV

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
04/10/2003 PLUMBING - FINAL Approved IVRS - Inspection 0000*
1.) GAS PRESSURE TEST IS OK
2.) GAS SHUT OFF VALVES OK
3.) WATER HTR FLU VENT, P & T VALVE & DRAIN IS OK
4.) FURANCE FLU VENT IS OK
5.) OK TO BACKFILL TRENCH.
04/08/2003 PLUMBING - FINAL Denied IVRS - Inspection 0999*
1.) MUST EXTEND RISER BY METER.
2.) MUST APPLY TAPE YELLOW PRIMER ON ALL FITTINGS AND WRENCH MARKS THEN APPLY 10-MIL TAPE.
3.) MUST EXTEND FLU VENT FOR WATER HTR 3' ABOVE COOLER.
4.) MUST REMOVE FLEX LINE IN P & T DRAIN AND INCREASE TO 3/4".
5.) MUST PROVIDE ROOF JACKS FOR ALL ROOF PENETRATIONS.
6.) MUST BLOCK GAS LINE AND STRAP DOWN EVERY 6'.
7.) RE TEST SYSTEM 10LBS MIN.