Permit: T03PL00615

Parcel: 119041390


Addresses:

3725 S 7TH AV 1M

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
04/24/2003 PLUMBING - FINAL Approved 1.) GAS PRESSURE TEST IS OK
2.) GAS SHUT OFF VALVES OK
3.) WATER HTR FLU VENT, P & T VALVES & DRAIN.
4.) WALL FURNACE FLU VENT IS OK.
04/23/2003 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection 0000*MUST REMOVED ALL ASBESTOS FLU VENTS AND INSTALL NEW B-VENTS & CAPS.
2.) MUST PROVIDE ADAQUET COMBUSTION RELIFE FOR ALL WATER HTRS ENCLOSURES.
3.) ALL FLU VENTS MUST TERMINATE AT LEAST 12" ABOVE ROOF.
4.) GAS PRESSURE TEST IS OK.
04/17/2003 PLUMBING - FINAL Denied IVRS - Inspection 0999*1.) MUST PROVIDE T CAPS FOR ALL WALL FURNACE FLU VENTS.
2.) MUST EXTEND ALL WATER HTR FLU VENTS THAT ARE LOCATED WITHIN 10' OF COOLERS 3' - 0" ABOVE COOLER SEE SECTION: 517.6 94 UPC.
3.) MUST REMOVE UNION IN LINE AND PROVIDE ON RIGHT & LEFT HAND NIPPLE SEE SECTION: 1211.10 94 UPC
4.) MUST PROVIDE VARIANCE FORM AND ACCEPTANCE OF ALTERNATE METHOD FOR P & T DRAIN. BY CITY OF TUCSON AND HAVE FORM ON SITE @ TIME OF INSPECTION.
5.) MUST PROVIDE AGA SHUT OFF VALVES FOR ALL APPLIANCES.
6.) MUST PROVIDE 2 10 X 10 OPENINGS FOR COMBUSTION AIR FOR WATER HTR ENCLOSURE SEE SECTION: 507.3.1. AND TABLE 5-1 94 UPC.
7.) MUST HAVE 1" CLEARANCE FROM COMBUSTIONABLE MATERIAL FOR WATER FLU VENT.