Inspection Status: Approved
Inspection History: PLUMBING - SEWER HCS CONNECT
| Date |
Description |
Inspector |
Results |
Comments |
| 09/07/2003 |
PLUMBING - SEWER HCS CONNECT |
|
Approved |
IVRS - Inspection 0000*/ 1) OK TO COVER |
| 08/29/2003 |
PLUMBING - SEWER HCS CONNECT |
|
Not ready for Inspection |
IVRS - Inspection 0000*/1) SEE 710.1 94 UPC. FIXTURES ABOVE THE NEXT UPSTREAM MANHOLE SHALL NOT DISCHARGE THROUGH A BACKWATER VALVE. 2) NOT READY FOR INSPECTION. |
| 08/28/2003 |
PLUMBING - SEWER HCS CONNECT |
|
Not ready for Inspection |
IVRS - Inspection 0000* |
| 08/25/2003 |
PLUMBING - SEWER HCS CONNECT |
|
Denied |
IVRS - Inspection 0999*/1) NO WATER TEST. 2) PIPE COVERED BEFORE INSPECTION. 3) BACK PITCHED SECTIONS NOT APPROVED. 4) USE APPROVED DRAINAGE FITTINGS. 5) THIS MAY NOT BE COMPLETE. |
| 06/03/2003 |
PLUMBING - SEWER HCS CONNECT |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ 1) NOT READY FOR INSPECTION |