Permit: T03PL00581

Parcel: 132090100

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
04/17/2003 PLUMBING - FINAL Approved IVRS - Inspection 0000*ALL CORRECTIONS HAVE BEEN MADE.
04/08/2003 PLUMBING - FINAL Denied IVRS - Inspection 0999*WATER HTR FLU VENT MUST EXTEND 3'-O" ABOVE COOLER WHEN B-VENT IS LOCATED WITHIN 10' OF FRESH AIR INTAKE SEE SECTION: 517.6 94 UPC.
04/04/2003 PLUMBING - FINAL Denied IVRS - Inspection 0999*
1.) NO ONE HOME!!
MUST HAVE ACCESS TO ALL APPLIANCE INSIDE.