Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T03PL00536
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/29/2003 | PLUMBING - FINAL | Approved | IVRS - Inspection 0000*/ 1) BY A SIMPLE REARRANGEMENT OF THE UNDER SINK PIPING, THE CONTINOUES WASTE CAN BE LOWERED SO THAT A BRANCH TAIL PIECE CAN BE USED AT THE STRAINER OUTLET. WE WILL NOT AUTOMATICALLY APPROVED SADDLE TAP FITTINGS IF THERE IS ANY OTHER POSSIBLE WAY TO CORRECT THE DRAIN | |
05/27/2003 | PLUMBING - FINAL | Denied | IVRS - Inspection 0999*/ 1) THE UNIT DRAIN MAY NOT BE DIRECTLY CONNECTED TO THE WASTE PIPING. SEE NOT FROM 5/1/03 2) DO NOT CALL IN THIS INSPECTION UNTIL ALL CORRECTIONS ARE MADE | |
05/01/2003 | PLUMBING - FINAL | Denied | IVRS - Inspection 0999*THERE IS STILL A CROSS CONNECTION FOR DISCHARGE HOSE FOR R.O. UNIT THERE IS A FAUCET SPOUT ON THE MARKET THAT WILL DISCHARGE THROUGH THE SPOUT INTO THE SINK. 2.) MUST REPLACE CONTINUOUS WASTE & TAIL PIECE FOR KITCHEN SINK 10MIL TAPE IS NOT ACCEPTABLE. |
|
03/24/2003 | PLUMBING - FINAL | Denied | IVRS - Inspection 0999* 1.) DISCHARGE DRAIN FOR R.O. UNIT CAN NOT CONNECT TO CONTINUOUS WASTE THIS IS A CROSS CONNECTION. 2.) OWNER OF HOUSE STATES THAT THERE IS DIFFERENT TASTE IN WATER. MUST FLUSH OUT SUPPLY LINES AND FILTERS. 3.) CAN NOT HAVE ABS SCH 40 EXPOSED TO ELEMENTS. THIS APPLICATION FOR DISCHARGE DRAIN FOR SOFTENER IS NOT TO CODE. |