Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T03PL00526
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/26/2003 | PLUMBING - FINAL | Approved | IVRS - Inspection 0000*/ 1) GAS PRESSURE TEST IS OK 2) GAS SHUT OFF VALVES OK 3) WATER HEATER FLU VENT, P & T VALVE AND DRAIN IS OK 4) FURNACE FLU VENT IS OK | |
06/18/2003 | PLUMBING - FINAL | Denied | IVRS - Inspection 0999*/ 1) GAS PRESSURE TEST IS OK 2) WATER HEATER FLUE VENT REQUIRES 1" CLEARANCE FROM COMBUSTIBLE MATERIAL 3) MUST EXTEND P & T DRAIN AND TERMINATE 6" ABOVE GRADE 4) MUST SCREW DOWN FLUE VENT FOR FURNACE AT SINGLE WALL TO DOUBLE WALL WITH (3) SHEET METAL SCREWS 5) MUST REMOVE FLEX LINE FOR P&T DRAIN AND RUN 3/4" ALL THE WAY TO VALVE 6) OK CONNECT APPLIANCES |