Permit: T03PL00517

Parcel: 130055860


Addresses:

2233 E 36TH ST

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
03/28/2003 PLUMBING - GAS PRESSURE TEST Approved
03/24/2003 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection 0999*
10 PSI TEST IS OK
1.) PROVIDE MIN 1" CLEARANCE AROUND WATER HEATER VENT.
2.) PROVIDE A DOOR ON WATER HEATER ENCLOSURE.
3.) T & P VALVE NOT WORKING. OWNER HAS CREATED AN UNSAFE CONDITION BY ADDING A BATHROOM TO THE SAME ROOM AS THE FURNACE. SEE SECTION 303.3 2000 IMC. "FUEL FIRED APPLIANCES SHALL NOT BE LOCATED IN, OR OBTAIN COMBUSTION AIR FROM A BATHROOM." FURNACE ALSO DOES NOT APPEAR TO BE IN GOOD WORKING CONDITION. TENANT HAS BEEN ADVISED NOT TO USE THE FURNACE UNTIL IT HAS BEEN RELOCATED & CHECKED OUT FOR SAFE OPERATION.