Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESSURE TEST
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/28/2003 | PLUMBING - GAS PRESSURE TEST | Approved | ||
| 03/24/2003 | PLUMBING - GAS PRESSURE TEST | Denied | IVRS - Inspection 0999* 10 PSI TEST IS OK 1.) PROVIDE MIN 1" CLEARANCE AROUND WATER HEATER VENT. 2.) PROVIDE A DOOR ON WATER HEATER ENCLOSURE. 3.) T & P VALVE NOT WORKING. OWNER HAS CREATED AN UNSAFE CONDITION BY ADDING A BATHROOM TO THE SAME ROOM AS THE FURNACE. SEE SECTION 303.3 2000 IMC. "FUEL FIRED APPLIANCES SHALL NOT BE LOCATED IN, OR OBTAIN COMBUSTION AIR FROM A BATHROOM." FURNACE ALSO DOES NOT APPEAR TO BE IN GOOD WORKING CONDITION. TENANT HAS BEEN ADVISED NOT TO USE THE FURNACE UNTIL IT HAS BEEN RELOCATED & CHECKED OUT FOR SAFE OPERATION. |