Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESSURE TEST
| Date |
Description |
Inspector |
Results |
Comments |
| 10/31/2003 |
PLUMBING - GAS PRESSURE TEST |
|
Approved |
IVRS - Inspection 0000*/ 1) 10 PSI TEST IS OK 2) OK TO BACKFILL TRENCH |
| 08/27/2003 |
PLUMBING - GAS PRESSURE TEST |
|
Denied |
IVRS - Inspection 0999*/1) WHERE UNIONS ARE NECESSARY, A RIGHT , LEFT NIPPLE AND COUPLING SHALL BE USED. 2) ALL VALVES TO BE AGA OR CSA APPROVED. 3) WATER HEATER REQUIRES AN ENCLOSURE. 4) T&P RELIEF VALVE INOPERABLE. 5) NEED TO SEE THE APPROVED VALVE FOR WATER HEATER. 6) REQUIRE CLEARANCE AROUND DOUBLE WALL VENT. 7) VENT TO EXTEND TO Z' ABOVE ROOF. 8) REQUIRE ACCESS TO BOTH HOUSES. 9) REQUIRE 10# TEST ON ENTIRE SYSTEM. |