Permit: T03PL00464

Parcel: 107112250


Addresses:

3015 N FONTANA AV

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
04/18/2003 PLUMBING - FINAL Approved IVRS - Inspection 0000*12PSI TEST IS OK
ALL CORRECTION HAVE BEEN MADE LEFT GAS CARD.
04/16/2003 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection 0000*10 PSI TEST IS OK OK TO BACKFILL TRENCH. WATER VENT NEEDS WORK NO CLEARANCE FROM WOOD. PROVIDE SHUT OFF VALUE AT UNION. EXTEND T & P DRAIN LINE TO 6" FROM GRADE. RETEST SYSTEM FOR NEW VALVE OR REVERSE THREAD FITTINGS.
PROVIDE AGA APPROVED VALVES AT STOVE & FURNACE.
03/20/2003 PLUMBING - FINAL Denied IVRS - Inspection 0999*1.) GAS SYSTEM NOT SIZED CORRECTLY PROPER SIZING SHOULD BE 1" PIPE.
2.) ADD NEW WATER HEATER TO THIS PERMIT. RECALL FOR INSPECTION.