Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/18/2003 | PLUMBING - FINAL | Approved | IVRS - Inspection 0000*12PSI TEST IS OK ALL CORRECTION HAVE BEEN MADE LEFT GAS CARD. |
|
| 04/16/2003 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection 0000*10 PSI TEST IS OK OK TO BACKFILL TRENCH. WATER VENT NEEDS WORK NO CLEARANCE FROM WOOD. PROVIDE SHUT OFF VALUE AT UNION. EXTEND T & P DRAIN LINE TO 6" FROM GRADE. RETEST SYSTEM FOR NEW VALVE OR REVERSE THREAD FITTINGS. PROVIDE AGA APPROVED VALVES AT STOVE & FURNACE. |
|
| 03/20/2003 | PLUMBING - FINAL | Denied | IVRS - Inspection 0999*1.) GAS SYSTEM NOT SIZED CORRECTLY PROPER SIZING SHOULD BE 1" PIPE. 2.) ADD NEW WATER HEATER TO THIS PERMIT. RECALL FOR INSPECTION. |