Permit: T03PL00434

Parcel: 130150730


Addresses:

4614 E JUAREZ ST

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
03/11/2003 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection 0000*
1. gas pressure test is ok
2. gas shut off valves ok
3. water htr flu vent, p & t valves is ok
4. wall furnace flu vent is ok.
03/06/2003 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection 0999*
1.) Must remove the union in line and replace with right & left hand nipple.
2.) Must extend p & t drain & terminate 6" above grade.
3.) Must use single wall flu vent for vent connector to water htr.
4.) Must screw down water htr flu vent with (3) sheet metal screws pre joint.
5.) Must provide 2- 10 x 10 fresh air supply on water htr enclosure 12" above ground and 12" below ceiling.
6.) Must provide AGA or CSA gas shut off valves for all appliances.
7.) Have system under test 10lbs min@ time of inspection.