Permit: T03PL00390

Parcel: 120076350

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESS TEST FNL

Date Description Inspector Results Comments
03/06/2003 PLUMBING - GAS PRESS TEST FNL Approved IVRS - Inspection 0000*
03/04/2003 PLUMBING - GAS PRESS TEST FNL Denied 1.) SINGLE WALL FLU VENT FOR WATER HTR REQUIRES 6" CLEARANCE FROM COMBUSTIONABLE MATERIAL.
2.) MUST PROVIDE 2 10X10 GRILLS FOR FRESH AIR COMBUSTION FOR WATER HTR ENCLOSURE.
3.) MUST ANCHOR 3/4" SUPPLY FOR RANGE.
4.) MUST SEAL PENETRATION OF GAS LINE FOR RANGE.
5.) GAS PRESSURE TEST IS OK
6.) MUST PROPERLY SEAL ROOF JACK WITH BLACK MASTIC.
2.)