Permit: T03PL00388

Parcel: 11904479A


Addresses:

3620 S 7TH AV

Inspection Status: Denied

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
02/28/2003 PLUMBING - FINAL Denied IVRS - Inspection 0999*
1) THERE ARE SOME SECTIONS OF GAS PIPING THAT DO NOT HAVE ANY MARKINGS ON PIPE. ALL MATERIALS MUST HAVE APPROVED STAMP OR MARKINGS SEE SECTION 3 01.1.2 94 UPC.
2) MUST PROVIDE APPROVED FLASHING FOR PENETRATION OF ROOF.
3) MUST PROVIDE APPROVED GAS SHUT OFF VALVE AND CONNECT TO GAS PACK ON ROOF.
4) MUST REPLACE P & T VALVES FOR WATER HEATERS.
5) MUST SCREW DOWN FLU VENTS FOR WATERHEATERS AND WALL FURNACE WITH 3 SHEET METAL SCREWS PER JOINT
6) CAN NOT HAVE A FLEX CONNECTOR PAST THROUGH CABINET WALLS OR SHELVES FOR RANGE.
7) MUST PROVIDE APPROVED GAS SHUT OFF VALVE FOR RANGE
8) MUST EXTEND FLU VENTS FOR WATER HEATERS 2' ABOVE WALL SEE SECTION: 517.3 94 UPC
9) MUST SECURE GAS DROP FOR WALL FURNACE.