Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESSURE TEST
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/20/2003 | PLUMBING - GAS PRESSURE TEST | Approved | IVRS - Inspection 0000* 1.) GAS PRESSURE TEST IS OK 2.) GAS SHUT OFF VALVES OK 3.) WATER HTR FLU VENT, P & T DRAIN & VALVE IS OK 4.) WALL FURNACE FLU VENT IS OK 5.) OK TO BACKFILL TRENCH. 6.) NOTE: OWNER MUST PROVIDE A ENCLOSURE FOR WATER HTR AS REQUESTED. |
|
| 03/19/2003 | PLUMBING - GAS PRESSURE TEST | Denied | IVRS - Inspection 0999*1.) Must use scotch coat pipe under ground. can not use blk steel pipe under ground by meter | |
| 03/18/2003 | PLUMBING - GAS PRESSURE TEST | Denied | IVRS - Inspection 0999*1.) MUST REMOVE UNION IN LINE AND REPLACE WITH RIGHT & LEFT HAND NIPPLE. 2.) MUST APPLY APPROVED TAPE PRIMER ON ALL JOINTS UNDER GROUND THEN APPLY 10MIL TAPE. 3.) MUST PROVIDE AGA OR CSA GAS SHUT OFF VALVES FOR ALL APPLIANCES 4.) MUST REPLACE P & T VALVE FOR WATER 5.) RE TEST SYSTEM 10LBS MIN. |
|
| 03/14/2003 | PLUMBING - GAS PRESSURE TEST | Denied | IVRS - Inspection 0999* |