Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T03PL00379
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/28/2003 | PLUMBING - FINAL | Approved | IVRS - Inspection 0000*24 PSI TEST OK ALL CORRECTIONS HAVE BEEN MADE. LEFT GAS CARD. |
|
| 02/26/2003 | PLUMBING - FINAL | Denied | IVRS - Inspection 0999* 1.) MUST USE RIGHT & LEFT HAND NIPPLES IN LIEU OF UNIONS SEE SECTION: 1211.10 94 UPC. 2.) B VENT FOR WATER HTR MUST TERMINATE 2'-0" ABOVE WALL SEE SECTION: 517.3 94 UPC. 3.) MUST SECURE GAS LINE DROP THAT SEEVES DRYERS AND COMPLETE THIS LINE INTO BLDG. 4.) MUST PROVIDE COMBUSTION AIR FOR WATER HTR RM SEE SECTION 507.3.1. 94 UPC. 5.) RE TEST SYSTEM. 6.) MUST SEAL GAS LINE PENETRATIONS INTO DWELLING. |