Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
02/24/2003 PLUMBING - FINAL Approved IVRS - Inspection 0000*ALL CORRECTIONS HAVE BEEN MADE. 30 PSI TEST OK LEFT GAS CARD.
02/20/2003 PLUMBING - FINAL Denied IVRS - Inspection 0999*25 PSI TEST
1.) PROVIDE A COMBUSTION AIR OPENINGT TO WITHIN 12" OF THE FLOOR IN WATER HEATER CLOSET. MUST BE MIN 100SQ. IN OPENING.
2.) GAS SHUT OFF VALVE MUST BE WITHIN 3' OF THE APPLIANCES CONNECTION ON FURNACE. RELOCATE VALVE & FLEX CONNECTOR.
3.) VENT CONNECTOR NOT CONNECTED TO FURNACE. ALL JOINTS MUST HAVE MIN 3 SCREWS.
4.) PROVIDE A CAP ON GAS VALVE WHERE FUTURE STOVE WILL BE INSTALLED. RETEST SYSTEM.