Permit: T03PL00326

Parcel: 130121840


Addresses:

3831 E 32ND ST

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
02/21/2003 PLUMBING - GAS PRESSURE TEST Approved 10PSI TEST IS OK
ALL CORRECTION HAVE BEEN MADE LEFT GAS CARD.
02/19/2003 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection 0999*PROVIDE MIN 1" CLEARANCE AROUND WATER HEATER VENT.
2.) REMOVE UNION OR PROVIDE A SHUT OFF VALVES
3.) CHANGE T & P VALVE.
4.) RETEST SYSTEM.
5.) INSTALL HEATER & WATER HEATER GAS SHUT OFF VALVES ARE O.K.