Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T03PL00298

Parcel: 10612056A

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T03PL00298

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/20/2003 PLUMBING - FINAL Approved IVRS - Inspection 0000*CORRECTIONS MADE OK
WATER PIPING INSTALLATION COMPLETE.
PLUMBING FINAL OK
RPPBP CERTIFICATION ON FILE W/TUCSON WATER.
05/18/2003 PLUMBING - FINAL Denied IVRS - Inspection 0999*/ 1) TRAILER #17 IS MISSING OR VACCUM BREAKER 2) PLEASE CHECK ALL HOSE BIBS
05/14/2003 PLUMBING - FINAL Denied IVRS - Inspection 0999*
YOU HAVE JUST FINISHED REPLACING THE ENTIRE WATER MAIN, AND ALL OF ITS BRANCHES. NOW YOU MUST PROTECT THE WATER SUPPLY LOY INSTALLING ATMOSPHERIC VACCUM BREAKERS ON EACH AND EVERY HOSE BIBB IN THE PARK. IF YOU FORGET ONE, I WILL FIND IT.
05/09/2003 PLUMBING - FINAL Denied 1.) PROVIDE CERTIFICATION OF BACKFLOW DEVICE
2.) OK TO COVER AREA AROUND METER PIPE AND CONNECTION OK
3.) ALL HOSE BIBBS IN THE PARK REQUIRE VACCUM BREAKERS CORRECLTY INSTALLED.
05/08/2003 PLUMBING - FINAL Denied IVRS - Inspection 0999*
1.) HAVE CERIFICATION FOR BACKFLOW DEVICE AT TIME OF NEXT INSPECTION.
2.) I REPEAT ALL ACTIVE HOSE BIBBS REQUIRE VACUUM BREAKERS
3.) SEE NOTE #1 FROM 5/2/03.