Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T03PL00298
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/20/2003 | PLUMBING - FINAL | Approved | IVRS - Inspection 0000*CORRECTIONS MADE OK WATER PIPING INSTALLATION COMPLETE. PLUMBING FINAL OK RPPBP CERTIFICATION ON FILE W/TUCSON WATER. |
|
05/18/2003 | PLUMBING - FINAL | Denied | IVRS - Inspection 0999*/ 1) TRAILER #17 IS MISSING OR VACCUM BREAKER 2) PLEASE CHECK ALL HOSE BIBS | |
05/14/2003 | PLUMBING - FINAL | Denied | IVRS - Inspection 0999* YOU HAVE JUST FINISHED REPLACING THE ENTIRE WATER MAIN, AND ALL OF ITS BRANCHES. NOW YOU MUST PROTECT THE WATER SUPPLY LOY INSTALLING ATMOSPHERIC VACCUM BREAKERS ON EACH AND EVERY HOSE BIBB IN THE PARK. IF YOU FORGET ONE, I WILL FIND IT. |
|
05/09/2003 | PLUMBING - FINAL | Denied | 1.) PROVIDE CERTIFICATION OF BACKFLOW DEVICE 2.) OK TO COVER AREA AROUND METER PIPE AND CONNECTION OK 3.) ALL HOSE BIBBS IN THE PARK REQUIRE VACCUM BREAKERS CORRECLTY INSTALLED. |
|
05/08/2003 | PLUMBING - FINAL | Denied | IVRS - Inspection 0999* 1.) HAVE CERIFICATION FOR BACKFLOW DEVICE AT TIME OF NEXT INSPECTION. 2.) I REPEAT ALL ACTIVE HOSE BIBBS REQUIRE VACUUM BREAKERS 3.) SEE NOTE #1 FROM 5/2/03. |