Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 05/22/2003 |
PLUMBING - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000* |
| 05/20/2003 |
PLUMBING - INTERMEDIATE |
|
Denied |
1) REMOVE OLD ASBESTOS VENT PIPE AND REPLACE WITH DOUBLE WALL PIPE. PROVIDE MINIMUM 1" CLEARANCE AROUND VENT AT ROOF PENETRATIONS. SINGLE WALL ELBOWS CONNECTING TO VENT PIPE MUST HAVE MINIMUM 6" CLEARANCE FROM COMBUSTIBLES. PROVIDE MINIMUM 3 SCREWS IN EACH JOINT 2) T&P DRAIN PIPE MUST EXTEND TO WITHIN 6" OF THE GROUND AND CANNOT HAVE THREADS AT END OF PIPE. CORRECT AND RECALL FOR INSPECTIONS |