Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/07/2003 | PLUMBING - FINAL | Approved | IVRS - Inspection 0000*TEST OK CALL GAS CO 889-1888. | |
| 02/06/2003 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection 0000*NOT READY FOR INSP. SEE SEC 1211.3. GAS PIPING SHALL BE KEPT AT LEAST 6" ABOVE GRADE. ALSO SEE SEC 1211.5 ALL HORIZONTAL PIPING SHALL HAVE 12" OF COVER. |