Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/04/2003 | PLUMBING - FINAL | Approved | 1.) GAS PRESSURE TEST IS OK 2.) GAS SHUT OFF VALVES OK 3.) WATER HTR FLU VENT P & T VALVE & DRAIN IS OK 4.) NOTE OWNER WILL PLUG & CAP GAS SUPPLY TO RANGE AND CUT OFF THREADS @ END OF P & T DRAIN. |
|
| 03/03/2003 | PLUMBING - FINAL | Denied | IVRS - Inspection 0999*1. THERE ARE FOUR APT'S AT 351 W. PENNSYLVANIA. NONE OF THEM HAS AN ADDRESS OR APT. NUMBER |
|
| 02/27/2003 | PLUMBING - FINAL | Denied | IVRS - Inspection 0999*NO ONE HOME NO ANSWER @ 490-5546. |
|