Permit: T03PL00186

Parcel: 12007263B


Addresses:

101 W DISTRICT ST

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
03/12/2003 PLUMBING - FINAL Approved IVRS - Inspection 0000*
1.) GAS PRESSURE TEST IS OK
2.) GAS SHUT OFF VALVES OK
3.) WATER HTR FLU VENT, P & T VALVE & DRAIN IS OK
4.) WALL FURNACE IS OK.
03/11/2003 PLUMBING - FINAL Denied IVRS - Inspection 0999*1.) Must provide AGA OR CSA approved gas shut off valves for all appliances.
2. Must provide 2 10 x 10 louver grills 12" down from ceiling and 12" above grade for fresh air combustion.
3. Re test system 10 lbs min.
4. Must screw down water htr flu vent with (3) sheet metal screws pre-joint.
5. MUst extend p & t drain & terminate 6" above grade.
02/14/2003 PLUMBING - FINAL Denied IVRS - Inspection 0999*