Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: SIGN SHOP
Permit Number - T03OT01980
Inspection Description - SIGN SHOP
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/22/2003 | SIGN SHOP | Approved | IVRS - Inspection 0000* | |
12/17/2003 | SIGN SHOP | Denied | IVRS - Inspection 0999*/ 1) WHERE IS SIGN LISTING AND MARKING 600.3, 600.4 2) SUPPORT FLEX CONDUIT AS PER CODE 3) TIGHTEN LOOSE GTO CONNECTIONS 4) PLEASE OPEN LETTERS FOR INSPECTION 5) A DISCONNECT SWITCH IS NEEDED PER 600.6 | |
11/25/2003 | SIGN SHOP | Not ready for Inspection | IVRS - Inspection 0000*/ 1) NO SIGN ON SITE-SPACE LOCKED |