Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 11/03/2003 |
BUILDING - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 10/22/2003 |
BUILDING - FINAL |
|
Partial Approval |
IVRS - Inspection 0000* 1) OCCUPANT LEAD INCORRECT. 2) REMOVE DEADBOLT FROM DOOR WITH PANIC BAR. 3) RESTROOMS REQUIRES LEVER HANDLES ON SINK & INSULATION KIT ON DRAIN PIPE. 4) DOOR & LATCH FOR RESTROOM REQUIRES A LEVER HANDLE THAT UNLOCKS AUTOMATICALLY FROM INSIDE. 5) ADAAG SIGNAGE REQUIRED FOR RESTROOM MOUNTED 60" TO CENTER OF SIGN FROM FLOOR ON WALL AT LATCH SIDE OF DOOR. |