Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Approved
Inspection History: SIGN ELECTRIC
| Date |
Description |
Inspector |
Results |
Comments |
| 02/17/2004 |
SIGN ELECTRIC |
|
Approved |
IVRS - Inspection 0000*/ 1) OK SIGN-BACK |
| 02/12/2004 |
SIGN ELECTRIC |
|
Partial Approval |
IVRS - Inspection 0000*/ OK FRONT SIGN. FINISH CORRECTIONS TO REAR SIGN. |
| 02/06/2004 |
SIGN ELECTRIC |
|
Partial Approval |
IVRS - Inspection 0000*/ BACK SIGN, FRONT SIGN, 1) USE APPROVED FITTINGS WITH SEAL TITE. 2) GROUND LOW VOLTAGE TRANSFORMER ENCLOSURE. 3) TRANSFORMER ENCLOSURES TO BE ASSESSABLE. 4) PRIMARY CONDUCTOR TO BE ISOLATED TO SWITCH AS PER PLAN STAMP. 5) LOW VOLTAGE CABLES TO BE SECURED TO ENCLOSURE. OK SIDE SIGN. |
| 01/08/2004 |
SIGN ELECTRIC |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) WAITING ON WEATHER PROOF ENCLOSURE 2) USE M/C FITTINGS 3) TIGHTEN LOOSE FITTINGS 4) OK SHOP |