Inspection Status: Approved
Inspection History: SIGN ELECTRIC
| Date |
Description |
Inspector |
Results |
Comments |
| 02/23/2004 |
SIGN ELECTRIC |
|
Approved |
IVRS - Inspection 0000* |
| 02/17/2004 |
SIGN ELECTRIC |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) COLOR CODE ALL CONDUCTORS ON PRIMARY SIDE TO MATCH VOLTAGE PER AMENDMENT 210.5 (C) 2) PLEASE PROVIDE ACCESS TO SIGNS FOR INSPECTION 3) PROVIDE A TERMINAL END FOR STANDARD GROUND WIRES AND TIGHTEN GROUND CONNECTIONS 4) PROVIDE MARKING LABEL ALL SIGNS AND WHERE ARE CITY PERMIT STICKERS FOR OTHER SIGNS |