Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 10/14/2003 |
BUILDING - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 10/08/2003 |
BUILDING - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000* 1) PERMIT GIVES DESCRIPTION AS "NO MORE THAN 60 STUDENTS" FLOOR PLAN IS FOR ONLY 1 OF 3 BUILDINGS WITH AN OCC OF THE ONE BLDG AS 50 (49 CLASSROOM,1 OFFICE) GROUP E OCC REQUIRE MANUAL ALARM SYSTEMS FOR 50 OR MORE. THERE ARE NO ALARMS AT THIS SITE.2) RESTROOMS DO NOT HAVE ADA HARDWARE NOR ADA SIGNAGE ( IBC CHAPTER 11). 3) EXTERIOR DOOR THRESHOLDS HAVE A STRIP ADDED THAT TAKES THEM OUT OF ADA COMPLIANCE. 4) EMERGENCY EGRESS LIGHTS DO NOT WORK AND THERE ARE NO ILLUMINATED EXIT SIGNS.(IBC 1003.2.10) (IBC 1003.2.11) |
| 10/06/2003 |
BUILDING - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000* SITE LOCKED. PLEASE RESCHEDULE |