Permit: T03OT01403

Parcel: 12807278A


Addresses:

712 S WILMOT RD

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
12/09/2003 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
10/08/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*/ 1) SIESMIC TIES ARE REQUIRED FOR THE 2X4 LAYIN RECESSED LIGHT FIXTURE. INSTALL PER CITY AMEND. TO NEC. 2) REVISE PLAN TO INDICATE THE ELECTRICAL PANELBOARD LOCATION, PANEL SCHEDULE, CIRCUITS AND AMP RATING. 3) JANITOR CLOSET LIGHT TO HAVE A SUITABLE LISTED/APPROVED COVER OR LENS AND HAVE ANY SHELVING A MIN. OF 12" AWAY. 4) OBTAIN PERMIT FOR A/C UNIT ADJACENT TO SERVICE EQUIPMENT AND LICENSED CONTRACTOR TO REDO TO CODE STANDARDS.