Permit: T03OT01333

Parcel: 113100050


Addresses:

2745 N CAMPBELL AV


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T03OT01333

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
01/16/2004 ELECTRIC - FINAL Approved IVRS - Inspection 0000*/ OK FOR C OF O. INSPECTORS REMINDER - NOTE ONLY - THE CABLE-IN-CONDUIT FROM MAIN PANEL TO SUB-PANEL MUST BE REPLACED WITH CONDUCTORS IN CONDUIT. THE CONDUCTORS MUST BE SIZED TO THE LOAD.
01/15/2004 ELECTRIC - FINAL Denied IVRS - Inspection 0210*/ CORRECTIONS 1) STRAP LOOSE CONDUITS, WALLS AND TOP OF WALK IN COOLER. 2) MARK THE PANEL DIRECTORY INDEX. EXTERIOR LOAD CENTER. 3) CORRECT THE CONDUIT LOCATED OUTSIDE ON NORTH WALL. THE FITTINGS ARE APART. 4) REMOVE THE THREE WIRE ALUMINUM CABLE FEEDING THE SUB PANEL INSIDE THE KITCHEN PREP AREA. INSTALL PROPER SIZE CONDUCTORS. INSTALL PROPER SIZE CONDUIT. RECALL INSPECTION WHEN READY.