Inspection History: ELECTRIC - FINAL
Permit Number - T03OT01333
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/16/2004 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000*/ OK FOR C OF O. INSPECTORS REMINDER - NOTE ONLY - THE CABLE-IN-CONDUIT FROM MAIN PANEL TO SUB-PANEL MUST BE REPLACED WITH CONDUCTORS IN CONDUIT. THE CONDUCTORS MUST BE SIZED TO THE LOAD. | |
01/15/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0210*/ CORRECTIONS 1) STRAP LOOSE CONDUITS, WALLS AND TOP OF WALK IN COOLER. 2) MARK THE PANEL DIRECTORY INDEX. EXTERIOR LOAD CENTER. 3) CORRECT THE CONDUIT LOCATED OUTSIDE ON NORTH WALL. THE FITTINGS ARE APART. 4) REMOVE THE THREE WIRE ALUMINUM CABLE FEEDING THE SUB PANEL INSIDE THE KITCHEN PREP AREA. INSTALL PROPER SIZE CONDUCTORS. INSTALL PROPER SIZE CONDUIT. RECALL INSPECTION WHEN READY. |