Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: SIGN SHOP
Permit Number - T03OT01312
Inspection Description - SIGN SHOP
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/21/2003 | SIGN SHOP | Approved | IVRS - Inspection 0000* | |
08/20/2003 | SIGN SHOP | Not ready for Inspection | IVRS - Inspection 0000*/ 1) 2700 E GRANT, NOT READY |