Permit: T03OT01149

Parcel: 10309074B


Addresses:

3871 N COMMERCE DR


Inspection Status: Approved

Inspection History: SIGN ELECTRIC

Permit Number - T03OT01149

Inspection Description - SIGN ELECTRIC

Inspection Status - Approved

Date Description Inspector Results Comments
11/10/2003 SIGN ELECTRIC Approved IVRS - Inspection 0000*
10/31/2003 SIGN ELECTRIC Denied IVRS - Inspection 0240*/ 1) THE SLEEVING OVER THE WIRES DOES NOT INDICATE IF IT IS SUNLIGHT RESISTANT. 2) PROVIDE MANUFACTURERS INFO. FOR THIS PRODUCT. IF NOT SUNLIGHT RESISTANT YOU WILL HAVE TO INSTALL A SHIELD OVER THE CABLE BUNDLES.
10/08/2003 SIGN ELECTRIC Denied IVRS - Inspection 0245*/ PER ART. 310 (NEC) SECTION 310-8, THE CONDUCTORS USED TO WIRE THE LETTERS TO THE TRANSFORMER/BALLAST JUNCTION BOX ARE NOT 'SUNLIGHT RESISTANT'. CONDUIT MUST BE INSTALLED AND JUNCTION BOXES USED AT EACH PENETRATION THRU THE WALL TO ENCLOSE THESE CONDUCTORS. THE INSTALLATION OF THE CONDUCTORS IS TFFN-MTW. SEE NEC TABLES 310-13, PAGE 70-122