Inspection History Details
Inspection Status: Approved
Inspection History: SIGN ELECTRIC
Permit Number - T03OT01149
Inspection Description - SIGN ELECTRIC
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/10/2003 | SIGN ELECTRIC | Approved | IVRS - Inspection 0000* | |
10/31/2003 | SIGN ELECTRIC | Denied | IVRS - Inspection 0240*/ 1) THE SLEEVING OVER THE WIRES DOES NOT INDICATE IF IT IS SUNLIGHT RESISTANT. 2) PROVIDE MANUFACTURERS INFO. FOR THIS PRODUCT. IF NOT SUNLIGHT RESISTANT YOU WILL HAVE TO INSTALL A SHIELD OVER THE CABLE BUNDLES. | |
10/08/2003 | SIGN ELECTRIC | Denied | IVRS - Inspection 0245*/ PER ART. 310 (NEC) SECTION 310-8, THE CONDUCTORS USED TO WIRE THE LETTERS TO THE TRANSFORMER/BALLAST JUNCTION BOX ARE NOT 'SUNLIGHT RESISTANT'. CONDUIT MUST BE INSTALLED AND JUNCTION BOXES USED AT EACH PENETRATION THRU THE WALL TO ENCLOSE THESE CONDUCTORS. THE INSTALLATION OF THE CONDUCTORS IS TFFN-MTW. SEE NEC TABLES 310-13, PAGE 70-122 |