Inspection History Details
Inspection Status: Denied
Inspection History: SIGN ELECTRIC
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/29/2003 | SIGN ELECTRIC | Denied | IVRS - Inspection 0999*/ 1) PLEASE UNCOVER CONDUIT RUN TO VERIFY DEPTH AS PER 300.5 2) M/C CABLE TO TERMINATE TO RACE WAY 3) MAINTAIN WORKING CLEARANCES AT PANEL 110.26 |