Inspection History Details
Inspection Status: Approved
Inspection History: SIGN ELECTRIC
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/25/2003 | SIGN ELECTRIC | Approved | IVRS - Inspection 0000* | |
| 03/21/2003 | SIGN ELECTRIC | Denied | IVRS - Inspection 0999*1.) SIGN COMPANY HAS MADE PROPER CONNECTIONS TO PROVIDED OUTLETS BUT. 2.) SUBSTANDARD EXISTING WIRING ON ROOF MUST BE REMOVED OR BROUGHT UP TO CODE. 3.) 4 X 4 J-BOX ON NORTH SIDE MUST BE PROPERLY SECURED. 4.) 4 X 4 J-BOX ON NORTH SIDE IS NOT BONDED TO EQUIPMENT GROUND. 5.) 240 V BREAKERS IN PANEL MUST BE SEPERATED. |
|
| 03/19/2003 | SIGN ELECTRIC | Denied | IVRS - Inspection 0999* 1.) IDENTIFY CIRCUITS TO NEW SIGNS. 2.) PROVIDE ROOF ACCESS. |
|
| 03/04/2003 | SIGN ELECTRIC | Not ready for Inspection | IVRS - Inspection 0000*1.) USA PAWN & JEWELRY 1 FLOURSCENT. 4 NEON ON RACEWAY 2-20A CIRCUIT MIN. |