Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
Permit Number - T03OT00017
Inspection Description - BUILDING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/21/2003 | BUILDING - FINAL | Approved | ||
02/18/2003 | BUILDING - FINAL | Denied | IVRS - Inspection 0999* 1.) SPACE #3' TALL REQUIRED OUTSIDE OF UNIT. 2.) EXIST SIGNS REQUIRED OVER DOORS LEADING OUT OF CLASS ROOM. 3.) ILLUMINATED EXIT SIGNS REQUIRED LEADING OUT OF MEETING ROOMS & RECEPTION. 4.) DOORS ALONG ANY ACCESSIBLE EGRESS ROUTE SHOULD BE LEVER HANDLE AND COME UNLOCKED FROM EGRESS SIDE WITHOUT ANY PINCHING OR TWISTING. 5.) NO THROW BOLTS OR SURFACE MOUNTED LATCHES ALLOWED ON EGRESS ROUTE (REMOVE FROM BATHROOM.) 6.) ADA RESTROOM REQUIRES BOTTOM OF SINK LIP TO BE MINIMUM 29" ABOVE FINISHED FLOOR WITH TOP O FSINK RIM TO BE MAXIMUM 34" A.F.F. 7.) ADA ACCESSIBILTY SIGN REQUIRED FOR RESTROOM. |