Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 01/26/2004 |
MECHANICAL - FINAL |
|
Approved |
IVRS - Inspection 0000*/ 1) CORRECTIONS HAVE BEEN MADE 2) PROVIDE A COMBO PERMIT FOR NEW FURNACE, A/C AND ELECTRIC CIRCUIT TO A/C. WILL LEAVE GAS CARD AFTER PERMIT AND INSPECTION ON NEW EQUIPMENT |
| 12/30/2003 |
MECHANICAL - FINAL |
|
Denied |
IVRS - Inspection 0999* |
| 12/26/2003 |
MECHANICAL - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) GAS FLEX TO UNIT ON ROOF CANNOT EXCEED 3' IN LENGTH. 2) PROVIDE ROOF JACKS AT ALL ROOF PENETRATIONS. 3) PAINT ALL EXPOSED PVC WITH LATEX PAINT. PROVIDE PLANS AND PERMITS FOR NEW FURNACE ENCLOSURE, NEW FURNACE AND AC, ELECTRICAL CIRCUIT AND GAS PIPE. WILL RELEASE GAS CLEARANCE AFTER THIS WORK HAS BEEN INSPECTED. |