Inspection Status: Denied
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 12/18/2003 |
MECHANICAL - FINAL |
|
Denied |
IVRS - Inspection 0999*/ NEW WTR HTR REQUIRES A SEPARATE PERMIT. T&P DRAIN LINE CANNOT RUN UPHILL TO THE ROOF. MUST GO TO DAYLIGHT. IF USING THE ALTERNATE METHOD, PROVIDE A PETITION OF APPEAL, [LEAVE ON SITE], FROM THE CODE ADMINISTRATOR. PROVIDE MIN. [3] SCREWS IN VENT CONNECTOR JOINTS. WILL RELEASE MECH. FINAL AFTER WTR HTR IS PERMITTED. |