Permit: T03ME00691

Parcel: 11706126A


Addresses:

650 E 9TH ST


Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T03ME00691

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
12/12/2003 MECHANICAL - FINAL Approved IVRS - Inspection 0000*
12/09/2003 MECHANICAL - FINAL Partial Approval IVRS - Inspection 0000*/ 1) NEED B-1 VENT PIPE TO BELOW CEILING TILES. 2) PROVIDE A RATED CEILING TILE ABOVE UNIT HTR OR 6" CLEAR, MIN. TOP OF HTR TO EXISTING TILE. 3) TIGHTEN GAS LINES AT UNIT HTR.