Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/22/2007 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 08/16/2007 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NEED TO SEAL HOLES IN CEILING WITH FIRE SEALANT 2) ALL OTHER CORRECTIONS MADE 3) NO ACCESS TO 3836 N. 2ND AVE |
|
| 08/08/2007 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. CAP OFF UNUSED GAS LINE IN CLOSET PROVIDE A SEDIMENT TRAP @ FURNACE RELOCATE GAS SHUT OFF VALVE 2. CAP OFF UNUSED VENT W/SHEET METAL PROVIDE MIN. 3 SCREWS IN ALL JOINTS OF FURNACE VENT CONNECTOR 3. PROVIDE A TRAP ON CONDENSATE DRAIN AND OVERFLOW SENSOR ON SECONDARY DRAIN 4. PROVIDE BUSHINGS IN EVAP. COIL REFER LINE CONNECTIONS 5. PROVIDE A SERVICE RECEPTACLE ON ROOF 6. REMOVE SINGLE WALL VENT EXTENSION ON ROOF AND USE DOUBLE WALL MIN. 3' ABOVE COMBUSTION AIR INTAKE 7. SECURE ELEC. CONDUIT ON ROOF 8. CONDENSATE CANNOT TERMINATE INTO A SEWER VENT |
|
| 12/02/2003 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0920* |