Inspection Status: Partial Approval
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 12/26/2003 |
MECHANICAL - FINAL |
|
Partial Approval |
IVRS - Inspection 0000* |
| 12/24/2003 |
MECHANICAL - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*/ UNIT A - OK. UNIT B - OK, NEW WTR HTR. T&P TO ROOF. UNIT C - OK, NO T&P ON WATER HTR [OLD]. UNIT D - NEW WTR HTR NEEDS T&P. EXTEND ALL VENTS WITHIN 10' OF EVAP COOLER. PROVIDE PERMITS FOR NEW WTR HTRS AND SCHEDULE AN INSP. PROVIDE PETITION OF APPEAL IF USING ALTERNATE METHOD FOR T&P DRAINS. |