Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 12/01/2003 |
MECHANICAL - FINAL |
|
Approved |
IVRS - Inspection 0000*/ CORRECTION OK. |
| 11/18/2003 |
MECHANICAL - FINAL |
|
Denied |
1) 3/8" ID GAS FLEX USED IS NOT ADEQUATE FOR 120, 000 BTU FURNACE. SEE LISTING ON GAS FLEX CONNECTOR. EVERYTHING ELSE LOOKS GOOD. RECALL FOR INSPECTION. NOTE: THIS JOB WAS CONTRACTED BY RITE WAY VETILATING CO. NOT RIGHT WAY PLUMBING |