Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T03ME00609
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/17/2003 | MECHANICAL - FINAL | Approved | IVRS - Inspection 0000*/ ALL CORRECTIONS HAVE BEEN MADE. | |
| 11/10/2003 | MECHANICAL - FINAL | Denied | CORRECTIONS HAVE NOT BEEN MADE | |
| 11/03/2003 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0999*/ 1) HEAT PUMP OVERFUSED AT 50 AMP. 35 AMP IS MAX FUSE SIZE. 2) LABEL WHICH HEAT STRIP WAS INSTALLED AND FUSE ACCORDINGLY. RECALL FOR INSPECTION. |