Permit: T03ME00608

Parcel: 133153170

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
11/19/2003 MECHANICAL - FINAL Approved IVRS - Inspection 0000*/ 3/8" i.d. x 18" GAS FLEX CONNECTORS NOT ADEQUATE FOR 100,000 BTU. SEE LISTING ON GAS FLEX CONNECTOR TAG. 3/8" I.D. X 12" WOULD HAVE BEEN OK FOR 102,000 BTU OR USE ½" I.D. OK FOR C OF O. JEFF WILL CHANGE CONNECTORS TODAY. I WILL CHECK AT MY EARLIEST CONVIENCE.
11/18/2003 MECHANICAL - FINAL Denied IVRS - Inspection 0999*/ 1) 3/8" ID GAS FLEX CONNECTOR NOT ADEQUATE FOR 100, 000 BTU FURNACE OR PROVIDE A LISTING FOR THE 2 BLACK CONNECTOR SHOWING OTHERWISE. THE STAINLESS STEEL FLEX ON THE WEST, UNIT IS OK. PROVIDE A GAS SHUT OFF VALVE WITHIN 3' OF CONNECTION TO A/C UNIT. REMOVE THE THREAD PROTECTOR FROM ONE OF THE GAS LINES AND USE AN APPROVED COUPLING 2) PROVIDE FRESH AIR INTAKES ON A/C UNITS 3) RECALL FOR INSPECTION