Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 11/18/2003 |
MECHANICAL - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 10/27/2003 |
MECHANICAL - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) PLASTIC HOSE FROM HUMIDIFIER CANNOT BE EXPOSED TO SUNLIGHT. CONNECTION TO PVC DRAIN LINE MUST BE A DIRECT CONNECTION WITH A FITTING. PLASTIC HOSE IS KINKED AT CONNECTIONS TO HUMIDIFIER. SEAL THE POP RIVETS AND SPOT WELDS ON TOP OF SHEET METAL DUCT ON ROOF. RECALL FOR INSPECTION |