Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T03ME00596
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/02/2003 | MECHANICAL - FINAL | Approved | IVRS - Inspection 0000*/ ALL CORRECTIONS HAVE BEEN MADE. | |
10/24/2003 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0999*/ 1) MARK UNIT DATA PLATES WITH PROPER HEAT STRIP AND FUSE ACCORDINGLY 2) TIGHTEN ALL LOOSE SEAL TITE FITTINGS 3) SEAL UNUSED OPENINGS INTO ELECTRIC DISCONNECTS 4) FRESH AIR INTAKE MUST BE 10' AWAY OR 2' LOWER THAN ANY SEWER OR EXHAUST VENTS 5) REPLACE DAMAGED SECTION OF SEWER VENT THAT HAS BEEN NOTCHED 6) BLOCK AND CLAMP PVC MAXIMUM 4' INTERVALS 7) PERMANENTLY LABEL EQUIPOMENT WITH ADDRESS. PAY A REINSPECTION FEE PRIOR TO NEXT INSPECTION | |
10/22/2003 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection 0000* |