Inspection Status: Denied
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 01/26/2004 |
MECHANICAL - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) INSULATION ON REFER LINES MUST HAVE CLEARANCE FROM FURNACE VENT. RELOCATE AS NEEDED. INSULATION COMING APART ON ROOF. GLUE ALL SEAMS. CIRCUIT FOR CONDENSOR IS TO LARGE AT 50 AMP. 40 AMP IS MAXIMUM. WIRE CONNECTIONS IN ELECTRIC DISCONNECT DO NOT FIT THE LUGS. SOME STRANDS ARE BROKEN, GROOVED OR NOT CONNECTED. SEAL AROUND REFER LINES AT ROOF JACK. RECALL FOR INSPECTION |
| 10/27/2003 |
MECHANICAL - FINAL |
|
Denied |
IVRS - Inspection 0920*/ 1) PLEASE HAVE YOUR CONTRACTOR CALL FOR AN INSPECTION WHEN SOMEONE WILL BE HOME |