Permit: T03ME00594

Parcel: 112042320


Addresses:

3115 N TERRELL PL

Inspection Status: Denied

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
01/26/2004 MECHANICAL - FINAL Denied IVRS - Inspection 0999*/ 1) INSULATION ON REFER LINES MUST HAVE CLEARANCE FROM FURNACE VENT. RELOCATE AS NEEDED. INSULATION COMING APART ON ROOF. GLUE ALL SEAMS. CIRCUIT FOR CONDENSOR IS TO LARGE AT 50 AMP. 40 AMP IS MAXIMUM. WIRE CONNECTIONS IN ELECTRIC DISCONNECT DO NOT FIT THE LUGS. SOME STRANDS ARE BROKEN, GROOVED OR NOT CONNECTED. SEAL AROUND REFER LINES AT ROOF JACK. RECALL FOR INSPECTION
10/27/2003 MECHANICAL - FINAL Denied IVRS - Inspection 0920*/ 1) PLEASE HAVE YOUR CONTRACTOR CALL FOR AN INSPECTION WHEN SOMEONE WILL BE HOME