Inspection Status: Denied
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 01/30/2004 |
MECHANICAL - FINAL |
|
Denied |
REFEE DUE/ CORRECTIONS FROM PREVIOUS INSP. HAVE BEEN IGNORED. MAKE NECESSARY CORRECTIONS BEFORE CALLING FOR RE-INSPECTION. |
| 11/21/2003 |
MECHANICAL - FINAL |
|
Denied |
IVRS - Inspection 0999*/ CCONDENSATE CANNOT DRAIN OVER THE EDGE OF THE ROOF. MUST GO TO WITHIN6 6" OF THE GROUND. USE A ROOF JACK IF DRILLING THROUGH THE ROOF. SECURE PIPE TO WALL. ALSO BLOCK AND CLAMP PVC ON ROOF MAX. 4' SPACING NOT 6' OR 7'. RECALL FOR INSPECTION |
| 11/17/2003 |
MECHANICAL - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) CONDENSATE DRAIN TRAP IS FLATTENED AT BOTTOM OF TRAP. PROVIDE A TRAP THAT IS 3/4" I.D. PAINT EXPOSED PVC WITH LATEX PAINT. BLOCK AND CLAMP PVC MAX. 4' INTERVALS. 2) BLOCK AND CLAMP NEW GAS PIPE ON ROOF. 3) 3/8" I.D. GAS FLEX NOT ADEQUATE FOR 120,000 BTU. 4) VIBRATION ISOLATORS ARE LAYING ON TOP OF THE UNIT. DOES HOMEOWNER WANT THESE INSTALLED? 5) CONDENSATE CANNOT DRAIN INTO A GUTTER THAT DISCHARGES ONTO A SIDEWALK. RECALL FOR INSPECTION. |