Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 10/28/2003 |
MECHANICAL - FINAL |
|
Approved |
IVRS - Inspection 0000*/ ALL CORRECTIONS HAVE BEEN MADE. |
| 10/17/2003 |
MECHANICAL - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) 3/8" I.D. GAS FLEX CONNECTOR ON ROOF NOT ADEQUATE FOR 120,000 BTU. FURNACE. USE 1/2" I.D. 2) SEWER VENT MUST BE 10' AWAY OR 2' ABOVE FRESH AIR INTAKE ON A/C UNIT. 3) PROVIDE A PERMIT FOR ELEC. UPGRADE AND INSPECTION. 4) SECURE CONDENSATE DRAIN LINE TO WALL. RE-CALL FOR INSPECTION. |