Permit: T03ME00573

Parcel: 136233180


Addresses:

6838 E BARROW ST

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
01/16/2004 MECHANICAL - FINAL Approved IVRS - Inspection 0000*/ CORRECTIONS HAVE BEEN MADE.
12/17/2003 MECHANICAL - FINAL Denied IVRS - Inspection 0999*/ EXTEND VENT CONNECTOR UP INTO DOUBLE WALL VENT PIPE AND PROVIDE MIN. [3] SCREWS IN EACH JOINT OF VENT CONNECTOR. 2) LABEL CICUIT BREAKER FOR CONDENSOR. 3) CLAMP ELEC. CONDUIT TO BLOCK ON ROOF. RECALL FOR INSPECTION.
10/08/2003 MECHANICAL - FINAL Denied IVRS - Inspection 0920*/ PLEASE HAVE YOUR CONTRACTOR CALL FOR AN INSPECTION WHEN THE HOMEOWNER WILL BE HOME.