Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 10/17/2003 |
MECHANICAL - FINAL |
|
Approved |
IVRS - Inspection 0000*/ ALL CORRECTIONS HAVE BEEN MADE. |
| 10/06/2003 |
MECHANICAL - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*/ #8 WIRE NOT ADEQUATE FOR 60 AMPS FROM ELEC. DICONNECT TO CONDENSOR. USE #6 WIRE OR CHANGE FUSES TO 50 AMP. RE CALL FOR INSPECTION. CONDENSOR ON SIDE OF HOUSE. |