Permit: T03ME00528

Parcel: 129021190


Addresses:

2926 E STRATFORD DR

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
10/10/2003 MECHANICAL - FINAL Approved IVRS - Inspection 0000*
09/24/2003 MECHANICAL - FINAL Denied IVRS - Inspection 0999*/ ROOF TOP PKG HT PUMP. 1) ELECT DATA PLATE ON UNIT NOT COMPLETED. DOES UNIT HAVE AUX. HT STRIP? YES? NO? IF NO, UNIT IS NOT CORRECTLY FUSED. COMPLETE AS NECESSARY. 2) PVC COND. PIPING EXPOSED TO SUN REQUIRES LATEX PAINT. COMPLETE/RECALL.